Over-Excitation Braking or Braking Resistor: Which One Should a VFD Use?

November 24, 2026
Últimas notícias da empresa sobre Over-Excitation Braking or Braking Resistor: Which One Should a VFD Use?

Introduction

When a motor-driven machine slows down, its stored mechanical energy does not disappear immediately. The rotating load can drive the motor like a generator and return energy to the VFD DC bus. If that energy accumulates faster than the drive can handle it, the DC-bus voltage rises and the VFD may trip on overvoltage.

Over-excitation braking and a braking resistor are two common ways to improve deceleration. They are not equivalent solutions. The correct choice depends on the amount of regenerative energy, stopping time, braking frequency, load direction, and thermal limits of the motor and braking components.

Why Does DC-Bus Overvoltage Occur During Deceleration?

During normal motoring, electrical energy flows from the supply through the VFD to the motor. During rapid deceleration, a high-inertia load continues rotating and drives the motor. The energy then flows back toward the DC bus. A standard diode-front-end VFD cannot normally return this energy to the power grid, so the DC voltage increases.

Extending the deceleration time reduces the rate of regenerated energy and is often the first adjustment to consider. However, some processes require a short stopping time, and some loads regenerate continuously or repeatedly. In those cases, an additional braking method is needed.

What Is Over-Excitation Braking?

Over-excitation braking increases motor excitation during deceleration so that part of the mechanical energy is converted into heat inside the motor. It can strengthen the braking effect without an external resistor and can be useful for occasional stops or moderate regenerative energy.

Its capacity is limited by the motor's thermal condition and by the control strategy of the drive. Repeated or prolonged use can increase motor temperature, and the available braking torque may not be sufficient for a high-inertia machine or a very short deceleration time. Over-excitation braking should therefore not be presented as a universal replacement for a braking resistor.

How Does a Braking Resistor Work?

A braking transistor or external braking unit monitors the DC-bus voltage and switches regenerated energy into a braking resistor. The resistor converts the electrical energy into heat outside the motor. This provides a defined path for larger or more frequent braking energy and helps prevent DC-bus overvoltage.

The resistor must be selected according to the drive specification, minimum permitted resistance, peak braking power, average power, and duty cycle. Some VFD ratings include a braking transistor, while others require an external braking unit. The resistor also needs adequate ventilation and safe clearance because its surface temperature can become very high.

When Is Over-Excitation Braking Suitable?

Over-excitation braking can be considered when stops are occasional, load inertia is moderate, the deceleration time is not extremely short, and the motor has sufficient thermal margin. Typical examples may include machines that need a firmer stop than a natural coast-down but do not generate large amounts of energy in every cycle.

It can also be useful when installation space is limited or an external resistor is undesirable. Even so, the motor temperature and actual stopping performance should be verified during commissioning. If overvoltage trips continue, simply increasing excitation is not a safe substitute for analyzing the braking energy.

When Should a Braking Resistor Be Used?

A braking resistor is usually the more appropriate choice for repeated rapid stops, large-inertia loads, short cycle times, or overhauling loads that can drive the motor. Examples include centrifuges, high-speed spindles, unwinders, reciprocating machines, and some crane or hoist movements.

For lifting applications, the resistor only manages electrical braking energy. It does not hold a suspended load and cannot replace a properly designed mechanical brake or safety system. If the load regenerates continuously or the braking energy is very large, a regenerative drive or active front end may be more suitable than a conventional resistor system.

Can Both Methods Be Used Together?

Depending on the VFD model and control strategy, over-excitation braking may be used together with a braking resistor. Motor loss can absorb part of the energy, while the resistor handles the energy that raises the DC bus above the braking threshold. This can improve deceleration performance in some applications.

However, combined operation does not remove the need to calculate resistor resistance, power, and duty cycle. The final selection should be based on the machine's maximum speed, total inertia, required stopping time, cycle frequency, and potential energy from vertical movement.

Common Selection and Installation Mistakes

Common mistakes include setting an unrealistically short deceleration time, choosing a resistor only by motor power, using resistance below the drive's permitted minimum, ignoring braking duty, or installing the resistor inside a poorly ventilated control cabinet. Connecting a resistor to a drive that requires an external braking unit is another serious error.

Commissioning should include repeated-stop testing under the heaviest expected load. Engineers should monitor DC-bus voltage, motor temperature, resistor temperature, stopping time, and fault history. Protective devices and wiring must follow the VFD and braking component manuals.

Choosing a Braking Method for VEIKONG Drives

VEIKONG drives provide braking functions according to the selected series and rating. When planning a system, users should confirm whether the drive has an internal braking transistor, requires an external braking unit, and supports the intended control function. The motor, VFD, resistor, and machine duty must be considered as one system.

Over-excitation braking is a practical option for moderate and intermittent deceleration, while a correctly sized braking resistor offers greater energy-handling capability for frequent or demanding stops. A clear calculation and real-load test will produce a safer and more reliable result than selecting either method by habit.